Easy control of the solid fuel boiler and hot water tank

Euroster 12P is an electronic, programmable controller for a solid fuel boiler with a screw feeder. Enables control of the screw feeder, blowing fan, central heating circulation pump and hot water tank loading pump. It has a weekly schedule of the boiler and hot water pump loading pump. The controller is equipped with anti-stop pump anti-stop system, which prevents seizing of the unused pump impeller. After the end of the heating season, the system automatically starts the pump every two weeks for 30 seconds (for the system to work after the season, the controller should be left turned on). Euroster 12P has a thermal protection and is adapted for installation in the boiler housing.


     

Advantages

  • Maintains the preset boiler temperature by controlling the blowing and operation of the feeder
  • Controls the operation of the central heating circulation pump
  • Manages the loading of the domestic hot water tank
  • Smooth blower fan speed regulation
  • Weekly work schedule of the boiler and the pump charging the domestic hot water tank
  • Possibility to connect a room regulator
  • Possibility of activating the priority for dhw heating
  • Lock before cooling the tank
  • Boiler, feeder and storage tank overheating protection
  • Registry of emergency situations
  • Thermal protection - additional protection increasing the safety of use
  • The Anti Stop system, cyclically activating the circulation pump every (outside the heating season) for approx. 30 seconds
  • Installation in the boiler housing

Downloads

EUROSTER 12P – instrukcja obsługi.pdf
EUROSTER 12P – karta katalogowa.pdf
EUROSTER 12P – deklaracja zgodności.pdf
EUROSTER 12P - catalog card.pdf
Balloon
Balloon

Technical data

Euroster 12P

Controlled device central heating pump, blower, hot water pump, screw feeder
Supply voltage 230 V 50 Hz
Maximum pump output load 2 A 230 V 50 Hz
Maximum blower output load 0.5 A 230 V 50 Hz
Maximum feeder output load 1 A 230 V 50 Hz
Power consumption 3 watts
Temperature measurement range from 0 ° C to + 100 ° C
DHW temperature adjustment range from + 20 ° C to + 90 ° C
Boiler temperature control range from + 40 ° C to + 90 ° C
Accuracy of temperature control 1 ° C
Hysteresis range 2 ° C - 5 ° C
Visual signaling backlit LCD display
Working temperature from + 5 ° C to + 40 ° C
Storage temperature from 0 ° C to + 50 ° C
Level of security IP 40
Colour black
Mounting method in the boiler housing
Driver mass with cables 0.45 kg
Standards, approvals, certificates compliance with EMC and LVD and RoHS directives
Warranty 2 years
Dimensions: width / height / depth (Mm) 175/114/52
Equipment Euroster 12P controller, manual, sensor bands, boiler temperature sensor with 1.5 m cable, feeder temperature sensor with 3 m cable, tank temperature sensor with 5 m cable, thermal protection cable - 1.5 m
Balloon
Balloon

Where to buy

You will find us easily
throughout the country

The Euroster Distributor Network is available throughout the country. Select a province from the list below and search for a Euroster distributor in your area. Do you want to become a Euroster distributor or are you our distributor and your company is not on the list? Contact us!

Customer service

tel. 65 571 15 16
Mon. - Fri: 7:00 a.m. - 4:00 p.m.

representatives

Please contact us
with our representatives
commercial

Service and support

Grzegorz Janusik
serwis@euroster.com.pl
tel. 65 571 20 12

Find a distributor

 
Program Inteligentny Rozwój Program Regionalny Samorząd woj. wielkopolskiego UE EFRR