Euroster 11M

Euroster 11M
Euroster 11M
Programmable three-way valve controller with servomotor and central heating circulation pump. It maintains the central heating circulation temperature at the set level or ensures proper water return temperature. Equipped with anti stop pump protection system.

Euroster 11M is a programmable controller for cooperation with a mixer and servomotor as well as a central heating circulation pump. In a central heating installation with a coal boiler, the controller automatically maintains a constant flow temperature or controls the valve and maintains a constant return temperature. Setting the optimal return temperature prevents the boiler from getting wet during water heating and increases its service life. The controller function is selected by software. In the central heating installation with a coal boiler, the regulator switches off the circulating pump after the boiler flame goes out. Euroster 11M has a pump stop protection system Anti Stop, which prevents the seizing process of the unused pump impeller. After the end of the heating season, the system automatically starts the pump every two weeks for 30 seconds (for the system to work after the season, the controller should be left turned on).

Benefits
  • The device is designed to work with a 3-way valve with servomotor and central heating circulation pump (the mixer servomotor must be equipped with limit switches).
  • Controlling the central heating circulation pump (based on the set flow temperature) or controlling the 3-way valve (based on the set return temperature) allows you to maintain a constant temperature in the central heating system
  • The optimal return temperature prevents the boiler from getting wet during water heating, which increases its service life
  • Driver function selected by software
  • Cooperation with a room regulator
  • Frost protection
  • Protection against overheating of water in the central heating system and the boiler
  • Pump and valve operation test
  • Correction of temperature indications
  • The Anti Stop System, which prevents the seizing process of the unused pump impeller, which starts the circulation pump (also outside the heating season) for approx. 30 seconds every 14 days
Technical specification
Controlled device mixing valve actuator, heating circulation pump
Supply voltage 230 V 50 Hz
Power consumption 1.6 watts
Maximum output load 3 A 230 V 50 Hz
Temperature measurement range from -5 ° C to + 110 ° C
Temperature adjustment range from + 20 ° C to + 70 ° C
Temperature regulation range - circulation temperature regulation mode from + 10 ° C to + 70 ° C
Accuracy of temperature control 1 ° C
Hysteresis range 2 ° C - 10 ° C
Visual signaling backlit LCD display
Working temperature from + 5 ° C to + 40 ° C
Storage temperature from 0 ° C to 65 ° C
Level of security IP 40
Colour black
Mounting method wall, wall plugs
Mass 0.76 kg
Standards, approvals, certificates compliance with EMC and LVD directives
Warranty 2 years
Dimensions: width / height / depth (Mm) 150/90/52
Equipment Euroster 11M controller, wall plugs, manual, mounting template, sensor bands
Selected other products from this category
Any questions? Do you need help selecting devices?

Our specialists are at your disposal. We will help you choose the right devices and prepare an offer for you.

Ask for an offer!
tel. +48 65 571 15 16
Mon-Fri: 7:00 - 16:00

Wholesale
Go to the list of our regional representatives
Where to buy
Search for the nearest distributor of EUROSTER devices. You can also shop directly in our online store.