Euroster 11Z is a programmable controller for simultaneous cooperation with a central heating circulating pump and a pump filling the domestic hot water tank - an economical solution in the case of the necessity of using two pumps in independent central heating and domestic hot water systems. gas. In the DHW system, the controller maintains a constant water temperature in the tank or in the domestic hot water system, with or without priority for tank loading. Euroster 11Z is equipped with Anti Stop pump protection system, which prevents the seizing process of the unused pump impeller. After the end of the heating season, the system automatically starts the pump every two weeks for 30 seconds (for the system to work after the season, the controller should be left turned on).
Controlled device | central heating and domestic hot water pump |
Supply voltage | 230 V 50 Hz |
Maximum output load | 3 A 230 V 50 Hz |
Power consumption | 1.6 watts |
Temperature measurement range | from -5 ° C to + 120 ° C |
Temperature adjustment range - central heating mode | from + 20 ° C to + 80 ° C |
Temperature adjustment range - DHW mode | from + 20 ° C to + 70 ° C |
Accuracy of temperature control | 1 ° C |
Hysteresis range | 2 ° C - 10 ° C |
Visual signaling | backlit LCD display |
Working temperature | from + 5 ° C to + 40 ° C |
Storage temperature | from 0 ° C to 65 ° C |
Level of security | IP 40, protection class II |
Colour | black |
Mounting method | wall, wall plugs |
Driver mass with cables | 0.72 kg |
Standards, approvals, certificates | compliance with EMC and LVD directives |
Warranty | 2 years |
Dimensions: width / height / depth (Mm) | 150/90/52 |
Equipment | Euroster 11Z controller, wall plugs, manual, mounting template, sensor bands |
Our specialists are at your disposal. We will help you choose the right devices and prepare an offer for you.
Ask for an offer!
tel. +48 65 571 15 16
Mon-Fri: 7:00 - 16:00