Euroster 11B is an electronic, programmable controller, designed to work with the pump charging the domestic hot water tank, recommended for heating installations with a solid fuel boiler. The controller maintains a constant water tank temperature - thanks to the measurement of the supply water temperature, it prevents the tank from cooling down in the event of the boiler going out. Euroster 11B is equipped with Anti Stop pump protection system, which prevents the seizing process of the unused pump impeller. After the end of the heating season, the system automatically starts the pump every two weeks for 30 seconds (for the system to work after the season, the controller should be left turned on).
Controlled device | DHW pump |
Supply voltage | 230 V 50 Hz |
Maximum load on each output | 3 A 230 V 50 Hz |
Power consumption | 1.6 watts |
Temperature measurement range | from -5 ° C to + 120 ° C |
Temperature adjustment range | from + 10 ° C to + 70 ° C |
Accuracy of temperature control | 1 ° C |
Hysteresis range | from 2 ° C to 10 ° C |
Visual signaling | backlit LCD display |
Working temperature | from + 5 ° C to + 40 ° C |
Storage temperature | from 0 ° C to + 65 ° C |
Level of security | IP 40 |
Colour | black |
Mounting method | wall, wall plugs |
Mass | 0.62 kg |
Standards, approvals, certificates | compliance with EMC and LVD directives |
Warranty | 2 years |
Dimensions: width / height / depth (Mm) | 150/90/52 |
Equipment | Euroster 11B controller, wall plugs, manual, mounting template, sensor bands |
Our specialists are at your disposal. We will help you choose the right devices and prepare an offer for you.
Ask for an offer!
tel. +48 65 571 15 16
Mon-Fri: 7:00 - 16:00